Used Chiller: BALTIMORE AIRCOIL DFCV EC9124-L613-E-AD of 2017


Search used machines

Similar Products:


Chiller - BALTIMORE AIRCOIL - DFCV EC9124-L613-E-AD

Data Sheet of Used BALTIMORE AIRCOIL DFCV EC9124-L613-E-AD

Ref. : 300039259

Brand: BALTIMORE AIRCOIL

Year: 2017

Other Specifications:

Air cooler with pre-chiller, completely new, still in its original packaging

THERMAL DATA
Required heating capacity (global/unit) (@ 100% RPM) : 200 / 200 kW
Available heating capacity (global/unit) (@ 100% RPM) : 260 / 259 kW
Fluid : H2O (Freezing point = 0°C; an antifreeze solution is required in negative climatic zone)
Required fluid flow rate (global/unitary) : 9.56 / 9.6 l/s
Available fluid flow rate (global/unit) : 12.4 / 12.4 l/s
Humid bulb air temperature : 24.0 °C
Dry bulb air temperature : 40.0 °C
Tipping point for the requested capacity : 26.0 °C
Fluid entrance temperature. : 32.0 °C
Fluid exit temperature : 27.0 °C
Mode of operation : adiabatic

ELECTRICAL DATA - UNITARY
Fan motor power : (8 x) 2.77 kW
Power absorbed by the fan motor (Net mechanical power at the motor shaft) (8 x) 2.77 kW
Voltage of the fan motor : 380-480 V
Current at full load at fan motor (at rated voltage) : (8 x) 4.28 A ( 380-480 V)
Synchronous speed of the fan motor : 1086 RPM